Elevator systems shall comply with the general requirements of Sections 57.4705.1.1 through 57.4705.1.8.
Each elevator vestibule shall be provided with an approved smoke detector located on the lobby ceiling. The elevator controls shall be designed so that the activation of a lobby smoke detector will cause all elevators serving that landing or floor to return non-stop to the designated main floor and be under manual control only.