SEC. 57.5706.4.10.5. STANDPIPE LOCATIONS.
 
   Sufficient standpipe outlets shall be located and installed so as to permit not less than two hose streams to protect any point on the wharf when each said outlet is equipped with not more than 350 feet of 1 1/2 inch fire hose. All standpipe outlets and fire hose shall have National Standard threads.