SEC. 57.315.3.8.1. STORED MATERIALS AND LIGHTING FIXTURES.
A clearance of at least 18 inches shall be maintained between stored materials and lighting fixtures.
SEC. 57.315.3.8.2. MATERIALS WHICH MAY SWELL OR EXPAND.
An unobstructed clearance of at least 2 feet shall be maintained between stored materials, which may swell or expand with the absorption of water, and building walls.
SEC. 57.315.3.8.3. MATERIALS SUSCEPTIBLE TO WATER DAMAGE.
Materials which are particularly susceptible to water damage shall be stored on skids, dunnage, pallets, or elevated platforms, maintaining at least 4 inches of clearance from the floor.
SEC. 57.315.3.8.4. DRAINAGE OF FLOOR.
Stored materials shall be arranged so as to allow drainage of floor areas through floor drains or wall scuppers.
SEC. 57.315.3.9. MATERIAL-HANDLING EQUIPMENT.
Motorized material-handling equipment shall be of a type designed for use in accordance with the hazards of the location in which it is used in compliance with NFPA 505. It shall be serviced, repaired, and stored in other than single storage areas.