SEC. 57.906.1.1. PORTABLE FIRE EXTINGUISHERS FOR ASSEMBLY OCCUPANCIES.
 
   In Group A Occupancies, one additional Class 2A portable fire extinguisher shall be provided as follows:
 
   1.   On each side of every stage or platform having an area greater than 1,000 square feet. Stages or platforms having an area of 1,000 square feet or less shall be provided with one extinguisher.
 
   2.   On each side of every fly gallery.
 
   3.   In basements beneath the stage or platform.
 
   4.   In every hallway or passageway leading to a dressing room.
 
   5.   In every property room, carpenter shop, or similar room.