SEC. 57.507.3.3. LAND USE.
 
   Land use and required fire-flow. See Table 57.507.3.3.
 
TABLE 57.507.3.3
RESPONSE DISTANCES THAT IF EXCEEDED REQUIRE THE INSTALLATION OF AN AUTOMATIC FIRE SPRINKLERS SYSTEM
 
 
Land Use *
Required Fire-Flow
Maximum Response Distance **
Engine Co.
Truck Co.
Low Density Residential
2,000 g.p.m. from three adjacent hydrants flowing simultaneously
1-1/2 miles
2 miles
High Density Residential and Commercial Neighborhood
4,000 g.p.m. from four adjacent hydrants flowing simultaneously
1-1/2 miles
2 miles
Industrial and Commercial
6,000 to 9,000 g.p.m. from four hydrants flowing simultaneously
1 mile
1-1/2 miles
High Density Industrial and Commercial or Industrial (Principal Business Districts or Centers)
12,000 g.p.m. available to any block (where local conditions indicate that consideration must be given to simultaneous fires, an additional 2,000 to 8,000 g.p.m. will be required)
3/4 mile
1 mile
 
*Land use designations are contained in the community plan elements of the General Plan for the City of Los Angeles.
 
**The maximum response distances for both L.A.F.D. fire suppression companies (engine and truck) must be satisfied.