SEC. 57.4701.3.1. MINIMUM REQUIREMENTS FOR TEMPORARY PLACE OF ASSEMBLAGE.
 
   In addition to other requirements in this article, the owner, manager, or person in control of an assembly event operating pursuant to a permit under Section 57.105.7.1.3 shall meet all of the following minimum requirements:
 
   1.   Before the issuance of the permit, provide to the Department documentation that all fire protective systems within the building or premise have been maintained and are functioning properly;
 
   2.   Before the issuance of the permit, provide to the Department a valid certificate of occupancy issued by the Department of Building and Safety for the applicable building;
 
   3.   Be physically present and provide constant supervision at the building or premise during the time that the assembly event is open to the public;
 
   4.   Comply with Chapter 8 of the California Fire Code and CCR Title 19, and provide flame certifications for all fabrics and decorations;
 
   5.   Provide and maintain exits, seating arrangements, exit signs, occupant loads, and access facilities in accordance with Sections 57.1001 through 57.1031; and
 
   6.   If an assembly event includes stages or platforms more than 30 inches above grade or temporary structures higher than 12 feet, procure a separate Temporary Installation permit in accordance with Section 91.106.1.3.1.