At least one passenger elevator shall be maintained in working order and accessible for immediate use by the Fire Department at all times.
The following San Francisco Fire Code section replaces the corresponding California Fire Code and International Fire Code Section:
Fuel oil storage inside buildings shall comply with Section 605.4.2.2 through 605.4.2.8 or Chapter 57. The currently adopted edition of NFPA 30 and NFPA 37 shall apply to all fuel-oil systems and fuel-oil generators regardless of fuel-oil quantity. The provisions of San Francisco Fire Department Administrative Bulletin 2.07 will apply to all fuel-oil systems and fuel-oil generators regardless of fuel-oil quantity.