18-29-607.1.2 Tempered water temperature control.
   Tempered water shall be controlled by one of the following:
   1.   A limiting device conforming to ASSE 1070/ASME A112.1070/CSA B125.70 and set to not greater than 100°F (43°C).
   2.   A thermostatic mixing valve conforming to ASSE 1017.
   3.   A water heater conforming to ASSE 1082.
   4.   A water heater conforming to ASSE 1084.
   This provision shall not supersede the requirement for protective shower valves in accordance with Section 18-29-424.
(Amend Coun. J. 10-14-21, p. 37722, Art. VI, § 27)