18-29-607.2.1.2 Demand recirculation controls for distribution systems.
   A water distribution system having one or more recirculation pumps that pump water from a heated water supply pipe back to the heated water source through a cold water supply pipe shall be a demand recirculation water system. Pumps shall have controls that comply with both of the following:
   1.   The control shall start the pump upon receiving a signal from the action of a user of a fixture or appliance, sensing the presence of a user of a fixture, or sensing the flow of hot or tempered water to a fixture fitting or appliance.
   2.   The control shall limit the temperature of the water entering the cold water piping to 104°F (40°C).
(Added Coun. J. 10-14-21, p. 37722, Art. VI, § 27)