Loading...
Water pressure booster systems shall be provided as required by Sections 18-29-606.5.1 through 18-29-606.5.10.
When the water pressure in the city water main is insufficient to furnish an adequate water supply for any purpose in any building, structure or premises, a hydropneumatic system, booster pump system, or gravity tank shall be installed.
Each compression tank shall be so connected that the air content thereof shall be no less than 25 percent of its total capacity. Each compression tank shall be provided with a sludge drain pipe which shall be connected to such tank at the lowest level of the bottom section thereof and shall discharge through an indirect connection into the drainage system with a minimum air gap of 6 inches (150 mm).
Booster pump systems may be of the constant speed type or the variable frequency drive type. Each pump or pumps shall have sufficient capacity to furnish an adequate supply of water for any purpose. When one pump is installed it shall run continuously or when a multipump system is installed the lead pump shall run continuously. A pressure reducing valve shall be installed on the discharge side of each constant speed pump.
Gravity tanks operating at atmospheric pressure shall be installed as required by Section 18-29-606.5.4.
Loading...