The water supply system shall be designed on the basis of the minimum available pressure at the water main or other source of water supply. The minimum available pressure will be given by the department of water management for each location.
(Amend Coun. J. 11-8-12, p. 38872, § 350)
In determining the available pressure to overcome friction in the piping system, head meter and other losses shall be deducted from the minimum available pressure source. When the pressure exceeds 100 psi (690 kPa) at any plumbing fixture, the pressure shall be reduced by an approved type reducing valve. The minimum size of fixture supply pipes are shown in Table 18-29-604.5.
Where individual pressure balancing in-line valves for individual fixture fittings are installed, such valves shall comply with ASSE 1066. Such valves shall be installed in a location with access. The valves shall not be utilized alone as a substitute for the balanced pressure, thermostatic or combination shower valves required by Section 18-29-424.3.
(Amend Coun. J. 10-14-21, p. 37722, Art. VI, § 14)