18-29-608.17.1.2 Direct connections.
   No pipe or system of piping in any building, structure, or premises, which receives its supply from the Chicago Waterworks System shall be directly connected to any device, appliance, or apparatus in which such water supply is used to provide power through a water jet or other device to create vacuum or partial vacuum with which to operate any aspirator, syphon, cellar drainer, ejector, cleaner, sweeper, conveyor, or washer of any kind or description.
18-29-609 Health Care Plumbing.
18-29-609.1 General.
   This section shall govern those aspects of health care plumbing systems that differ from plumbing systems in other structures. Health care plumbing systems shall conform to the requirements of this section in addition to the other requirements of this Article.
18-29-609.1.1 Where required.
   The provisions of this section shall apply to the special devices and equipment installed and maintained in the following occupancies: nursing homes, homes for the aged, orphanages, infirmaries, first aid stations, psychiatric facilities, clinics, professional offices of dentists and doctors, mortuaries, educational facilities, surgery, dentistry, research and testing laboratories, establishments manufacturing pharmaceutical drugs and medicines, and other structures with similar apparatus and equipment classified as plumbing.
18-29-609.2 Water service.
   All hospitals shall have two water service pipes installed in such a manner so as to minimize the potential for an interruption of the supply of water in the event of a water main or water service pipe failure.
18-29-609.3 Hot water.
   Hot water shall be provided to supply all of the hospital fixture, kitchen and laundry requirements. Special fixtures and equipment shall have hot water supplied at a temperature specified by the manufacturer. The hot water system shall be installed in accordance with Sections 18-29-607 through 18-29-607.6.
18-29-609.4 Vacuum breaker installation.
   Vacuum breakers shall be installed a minimum of 6 inches (150 mm) above the flood level rim of the fixture or device in accordance with Sections 18-29-608 through 18-29-608.17.1.2. The flood level rim of hose connections shall be the maximum height at which any hose is utilized.
18-29-609.5 Prohibited water closet and clinical sink supply.
   Jet- or water-supplied orifices, except those supplied by the flush connections, shall not be located in or connected with a water closet bowl or clinical sink. This section shall not prohibit an approved bidet installation.
(Amend Coun. J. 11-8-12, p. 38872, § 355)
18-29-609.6 Clinical, hydrotherapeutic and radiological equipment.
   All clinical, hydrotherapeutic, radiological or any equipment that is supplied with water or that discharges to the waste system shall conform to the requirements of this section and Sections 18-29-608 through 18-29-608.17.1.2.