Loading...
Where a storage water heater is supplied with cold water that passes through a check valve, pressure reducing valve or backflow preventer, a thermal expansion control device shall be connected to the water heater cold water supply pipe at a point that is downstream of all check valves, pressure reducing valves and backflow preventers. Thermal expansion tanks shall be sized in accordance with the tank manufacturer's instructions and shall be sized such that the pressure in the water distribution system shall not exceed that required by Section 18-29-604.8.
(Amend Coun. J. 10-14-21, p. 37722, Art. VI, § 27)
Fixture fittings, faucets and diverters shall be installed and adjusted so that the flow of hot water from the fittings corresponds to the left-hand side of the fixture fitting.
Exception: Shower and tub/shower mixing valves conforming to ASSE 1016/ASME A112.1016/CSA B125.16 or ASME A112.18.1/CSA B125.1, where the flow of hot water corresponds to the markings on the device.
(Amend Coun. J. 10-14-21, p. 37722, Art. VI, § 27)
For other than Group R-2, R-3, R-4 and R-5 occupancies that are four stories or less in height above grade plane, piping to the inlet of a water heater and piping conveying water heated by a water heater shall be insulated in accordance with Section C404.4 of the Chicago Energy Conservation Code. For Groups R-2, R-3, R-4 and R-5 that are four stories or less in height above grade plane, piping to the inlet of a water heater and piping conveying water heated by a water heater shall be insulated in accordance with Section R403.5.3 of the Chicago Energy Conservation Code.
(Amend Coun. J. 10-14-21, p. 37722, Art. VI, § 27)
Mechanical expansion joints may be used where necessary to provide for expansion and contraction of piping. Access to mechanical expansion joints shall be provided. For hot water piping, the expansion function shall be provided by the flexing of the piping material with expansion loops or swing joints. The piping shall be properly anchored and installed as follows:
1. Each hot water riser shall be provided with anchors at a maximum distance of 100 feet (30.5 m) with an expansion loop of adequate length provided between such anchors.
2. Each hot water main shall be provided with anchors at a maximum distance of 100 feet (30.5 m) with an expansion loop of adequate length provided between such anchors. Offsets of 90 degrees in a horizontal main shall be of adequate length to absorb expansion by flexure.
3. Branches from mains connected to risers shall be provided with a swing joint of adequate length unless the branch is of adequate length to absorb expansion by flexure.
4. Branches from risers to fixtures shall be provided with a swing joint of adequate length unless the branch is of adequate length to absorb expansion by flexure.
(Amend Coun. J. 10-14-21, p. 37722, Art. VI, § 27)
Loading...