Where individual pressure balancing in-line valves for individual fixture fittings are installed, such valves shall comply with ASSE 1066. Such valves shall be installed in a location with access. The valves shall not be utilized alone as a substitute for the balanced pressure, thermostatic or combination shower valves required by Section 18-29-424.3.
(Amend Coun. J. 10-14-21, p. 37722, Art. VI, § 14)
The installation of a water service pipe shall be prohibited in soil and ground water contaminated with solvents, fuels, organic compounds or other detrimental materials causing permeation, corrosion, degradation or structural failure of the piping material. Where detrimental conditions are suspected, a chemical analysis of the soil and ground water conditions shall be required to ascertain the acceptability of the water service material for the specific installation. Where detrimental conditions exist, approved alternative materials or routing shall be required.
Pipe, pipe fittings, joints, valves, faucets and fixture fittings utilized to supply water for drinking or cooking purposes shall comply with NSF 372 and shall have a weighted average lead content of 0.25 percent or less.
(Added Coun. J. 10-14-21, p. 37722, Art. VI, § 15)
* Editor's note – Coun. J. 10-14-21, p. 37722, Art. VI, § 15, numbered this section as 605.3.1; renumbered as § 18-29-605.3.1 at the discretion of the editor. Future legislation will correct if needed.