Loading...
New and replacement water closets, urinals, shower heads, weather-based irrigation controllers, spray sprinkler bodies, commercial pre-rinse spray valves and private residential lavatory faucets shall meet the specifications required for the United States Environmental Protection Agency's WaterSense program label and shall bear such label or be approved in accordance with this chapter.
(Added Coun. J. 10-14-21, p. 37722, Art. VI, § 8)
The minimum size of a fixture supply pipe shall be as shown in Table 18-29-604.5. The fixture supply pipe shall not terminate more than 30 inches (762 mm) from the point of connection to the fixture. A reduced-size connector installed between the supply pipe and the fixture shall be of approved type. The supply pipe shall extend to the floor or wall adjacent to the fixture.
Fixture | Minimum Pipe Size (inch) |
Fixture | Minimum Pipe Size (inch) |
Bathtubs (60" by 32" and smaller) | 1/2 |
Bathtubs (larger than 60" by 32") | 1/2 |
Bidet | 3/8 |
Combination sink and tray | 1/2 |
Dishwashing machine (domestic) | 1/2 |
Drinking fountain | 3/8 |
Hose bibbs | 1/2 |
Kitchen sink | 1/2 |
Laundry, 1, 2 or 3 compartments | 1/2 |
Lavatory | 3/8 |
Shower, single head | 1/2 |
Sinks, flushing rim | 3/4 |
Sinks, service | 1/2 |
Urinal, flush tank | 1/2 |
Urinal, flushometer valve | 3/4 |
Wall hydrant | 1/2 |
Washing machine (automatic) | 1/2 |
Water closet, flush tank | 3/8 |
Water closet, flushometer valve | 1 |
Water closet, flushometer tank | 3/8 |
Water closet, one piece | 1/2 |
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 psi = 6.895 kPa.
(Amend Coun. J. 10-14-21, p. 37722, Art. VI, § 10)
The minimum size of individual distribution lines utilized in parallel water distribution systems shall be as shown in Table 18-29-604.5.
Wherever water pressure from the street main or other source of supply is insufficient to provide flow pressures at fixture outlets as required under Section 18-29-604.3, a water pressure booster system conforming to Section 18-29-606.5 shall be installed on the building water supply system.
Where water pressure within a building exceeds 100 psi (690 kPa) static at any fixture or outlet, an approved water pressure reducing valve conforming to ASSE 1003 with strainer shall be installed to reduce the pressure at any fixture or outlet in the building water distribution piping to 100 psi (690 kPa) static or less.
Loading...