The route to public toilet facilities shall not pass through kitchens, storage rooms or closets. Access to required toilet facilities shall be from within the building. The public shall have access to the required toilet facilities at all times when the building or tenant space is occupied.
Exception: Toilet facilities for storage structures, unconditioned spaces, and kiosks may be located in adjacent buildings under the same ownership.
(Added Coun. J. 10-14-21, p. 37722, Art. IV, § 7)
Required public and employee toilet facilities shall be located not more than one story above or below the space required to be provided with toilet facilities and the path of travel to such facilities shall not exceed 500 feet (152 m).
Exception: The location and maximum distance of travel to required employee facilities in factory, industrial and storage occupancies shall be permitted to exceed that required by this section where the location and maximum distances are approved by the Building Commissioner.
(Added Coun. J. 10-14-21, p. 37722, Art. IV, § 7)
Drinking fountains shall not be required to be located in individual tenant spaces provided that public drinking fountains are located within a path of travel of 500 feet (152 m) of the most remote location in the tenant space and not more than one story above or below the tenant space.
(Amend Coun. J. 10-14-21, p. 37722, Art. IV, § 7)