Each urinal utilized by the public or employees shall occupy a separate area with walls or partitions to provide privacy. The horizontal dimension between walls or partitions at each urinal shall be not less than 30 inches (762 mm). The walls or partitions shall begin at a height not greater than 12 inches (305 mm) from and extend not less than 60 inches (1524 mm) above the finished floor surface. The walls or partitions shall extend from the wall surface at each side of the urinal not less than 18 inches (457 mm) measured from the finished backwall surface or to a point not less than 6 inches (152 mm) beyond the outermost front lip of the urinal, whichever is greater.
(Added Coun. J. 10-14-21, p. 37722, Art. IV, § 11)