Lavatories shall conform to ASME A112.19.1/CSA B45.2, ASME A112.19.2/CSA B45.1, ASME A112.19.3/CSA B45.4 OR CSA B45.5/IAPMO Z124. Group wash fixtures shall conform to the requirements of Section 18-29-402. For determining the number of lavatories required by Table 18-29-403.1, every 20 inches (500 mm) of rim space of a group wash fixture shall be considered as one lavatory.
(Amend Coun. J. 10-14-21, p. 37722, Art. IV, § 17)
Lavatories and group wash fixtures shall have waste outlets not less than 1 1/4 inches (32 mm) in diameter. A strainer, pop-up stopper, crossbar or other device shall be provided to restrict the clear opening of the waste outlet.
(Amend Coun. J. 10-14-21, p. 37722, Art. IV, § 17)
Tempered water shall be delivered from lavatories and group wash fixtures located in public toilet facilities. Tempered water shall be delivered through a water-temperature limiting device that conforms to ASSE 1070/ASME A112.1070/CSA B125.70.
(Added Coun. J. 10-14-21, p. 37722, Art. IV, § 17)
Prefabricated showers and shower compartments shall conform to ANSI Z124.2, ASME A112.19.9 or CSA B45.5. Shower valves for individual showers shall conform to the requirements of Section 18-29-424.4.