Section R302.3 Two-family dwellings, of the IRC, is hereby amended by deleting said section and exceptions and inserting in lieu thereof the following section:
R302.3 Two-family dwellings For purposes of fire-resistive separation, two-family dwelling units shall be considered as townhouse units and shall be constructed in accordance with R302.2
Section R302.6, Dwelling/garage fire separation, of the IRC, is hereby amended by deleting said section and inserting in lieu thereof the following section:
Section R302.6 Dwelling/garage fire separation The garage shall be separated throughout as required by Table R302.6. Openings in garage walls shall comply with section R302.5.
Table R302.6 Dwelling/Garage Separation, of the IRC, is hereby amended by modifying said table as follows:
Table R302.6, Dwelling/garage separation
Separation | Material |
From the residence & attics – common wall with garage | 5/8” “X” fire code sheetrock or equivalent applied to the garage side |
From all habitable rooms above the garage | 5/8” “X” fire code sheetrock or equivalent – throughout garage |
Structures supporting floor/ceiling assemblies used for separation required by this section | 5/8” “X” fire code sheetrock or equivalent – throughout garage |
Detached garages located less than six feet (6’) from a dwelling unit(s) on the same lot | 5/8” “X” fire code sheetrock or equivalent – throughout garage |
Section R302.13, Fire Protection of Floors, of the IRC, is hereby amended by deleting exception 4 and inserting in lieu thereof the following:
Section R302.13 exception 4 Approved floor assemblies demonstrating equivalent fire performance by an approved testing company showing length and time duration for exposure to fire. It shall be defined by performance equivalent to 26 minutes using ASTM E119 standard fire endurance testing with a superimposed load simulating a maximum load condition (i.e. 100% design load).
Section R303.3, Bathrooms, of the IRC, is hereby amended by deleting said section and inserting in lieu thereof the following section and also by adding the following exception:
Section R303.3 Bathrooms Bathrooms shall be provided with a mechanical ventilation system. The minimum ventilation rates shall be 50 cfm for intermittent ventilation or 20 cfm for continuous ventilation. Ventilation air from the space shall be exhausted directly to the outside.
Exception: Toilet rooms containing only a water closet and/or lavatory may be provided with a recirculating fan.