184.21 SUBSECTION TABLE R302.1(1) AMENDED - EXTERIOR WALLS.
Table R302.1(1), Exterior Walls, of the IRC, is hereby amended by modifying said table as follows:
Exterior Wall Element
Minimum Fire-Resistance Rating
Minimum Fire Separation Distance
Walls
(Fire-resistance rated)
Dwellings - 1 hour - tested in accordance with ASTM E119, UL 263 or Section 703.3 of the International Building Code with exposure from both sides
< 5 feet
(Fire-resistance rated)
Accessory Structures - 1 hour - tested in accordance with ASTM E119, UL 263 or Section 703.3 of the International Building Code with exposure from both sides
< 3 feet
(Not fire-resistance rated)
Dwellings - 0 hours
5 feet
(Not fire-resistance rated)
Accessory Structures - 0 hours
3 feet
Projections
(Fire-resistance rated)
Dwellings - 1 hour on the underside, or heavy timber, or fire-retardant-treated wood
< 3 feet
(Fire-resistance rated)
Accessory Structures - 1 hour on the underside, or heavy timber, or fire-retardant-treated wood<2 feet
<2 feet
(Not fire-resistance rated)
Dwellings - 0 hours
3 feet
(Not fire-resistance rated)
Accessory Structures - 0 hours
2 feet
Openings
Not allowed
N/A
< 3 feet
25% Maximum Wall Area
0 hours
3 feet
Unlimited
0 hours
5 feet
Penetrations
All
Comply with Section R302.4
< 3 feet
None required
3 feet