184.38 SECTION R403.1.4.1 - AMENDED - FROST PROTECTION.  
Section R403.1.4.1, Frost Protection, of the IRC, is hereby amended by deleting all existing exceptions and inserting in lieu thereof the following exception:
Section R403.1.4.1 Frost protection exception Detached garages of light frame wood construction of 1,010 square feet or less in size and detached garages of 400 square feet or less in size of other than light frame wood construction and not located entirely within the buildable area of the lot may be provided with a floating slab. The floating slab shall include a thickened slab edge of a minimum twelve (12) inches thick. Six inches of the thickened slab shall be below grade and six inches shall be above finished grade. The bottom portion of the thickened slab area shall be twelve (12) by twelve (12) inches. Two #4 rebar shall be placed within the thickened edge continuous around the perimeter of the slab. Floors shall be of Portland cement concrete not less than 4 inches thick. Garages areas shall have all sod and/or debris removed prior to installation of said floor.