184.22 R302.3 AMENDED - TWO-FAMILY DWELLINGS.
Section R302.3 Two-family dwellings, of the IRC, is hereby amended by deleting said section and exceptions and inserting in lieu thereof the following section:
R302.3 Two-family dwellings For purposes of fire-resistive separation, two-family dwelling units shall be considered as townhouse units and shall be constructed in accordance with R302.2
184.23 SECTION R302.6 AMENDED - DWELLING/GARAGE FIRE SEPARATION.
Section R302.6, Dwelling/garage fire separation, of the IRC, is hereby amended by deleting said section and inserting in lieu thereof the following section:
Section R302.6 Dwelling/garage fire separation The garage shall be separated throughout as required by Table R302.6. Openings in garage walls shall comply with section R302.5.
184.24 SECTION TABLE R302.6 AMENDED - DWELLING/GARAGE SEPARATION.
Table R302.6 Dwelling/Garage Separation, of the IRC, is hereby amended by modifying said table as follows:
Table R302.6, Dwelling/garage separation
 
Separation
Material
From the residence & attics – common wall with garage
5/8” “X” fire code sheetrock or equivalent applied to the garage side
From all habitable rooms above the garage
5/8” “X” fire code sheetrock or equivalent – throughout garage
Structures supporting floor/ceiling assemblies used for separation required by this section
5/8” “X” fire code sheetrock or equivalent – throughout garage
Detached garages located less than six feet (6’) from a dwelling unit(s) on the same lot
5/8” “X” fire code sheetrock or equivalent – throughout garage
 
184.25 AMENDED - FIRE PROTECTION OF FLOORS.
Section R302.13, Fire Protection of Floors, of the IRC, is hereby amended by deleting exception 4 and inserting in lieu thereof the following:
Section R302.13 exception 4 Approved floor assemblies demonstrating equivalent fire performance by an approved testing company showing length and time duration for exposure to fire. It shall be defined by performance equivalent to 26 minutes using ASTM E119 standard fire endurance testing with a superimposed load simulating a maximum load condition (i.e. 100% design load).
184.26 SECTION R303.3 AMENDED - BATHROOMS.
Section R303.3, Bathrooms, of the IRC, is hereby amended by deleting said section and inserting in lieu thereof the following section and also by adding the following exception:
Section R303.3 Bathrooms Bathrooms shall be provided with a mechanical ventilation system. The minimum ventilation rates shall be 50 cfm for intermittent ventilation or 20 cfm for continuous ventilation. Ventilation air from the space shall be exhausted directly to the outside.
Exception: Toilet rooms containing only a water closet and/or lavatory may be provided with a recirculating fan.
184.27 SECTION R305.1.1 AMENDED - BASEMENTS.
Section R305.1.1, Basements, of the IRC, is amended deleting the exception and inserting in lieu thereof:
Section R305.1.1 exception Existing basements not having a height as specified in this section are allowed to be finished with a ceiling height that is not decreased more than the minimal measurement created by applying a finished ceiling of gypsum board or acoustical ceiling tiles.
184.28 SECTION R308.4.2 AMENDED- GLAZING ADJACENT TO DOORS.
Section R308.4.2, Glazing Adjacent To Doors, of the IRC, is hereby amended by deleting said section and items #1 and #2 and inserting in lieu thereof the following (exceptions remain unchanged):
Section R308.4.2 Glazing Adjacent To Doors Glazing in an individual fixed or operable panel adjacent to a door where the nearest vertical edge of the glazing is within a 24-inch (610 mm) arc of either vertical edge of the door in a closed position and where the bottom exposed edge of the glazing is less than 60 inches (1524 mm) above the walking surface shall be considered to be a hazardous location.