184.25 AMENDED - FIRE PROTECTION OF FLOORS.
Section R302.13, Fire Protection of Floors, of the IRC, is hereby amended by deleting exception 4 and inserting in lieu thereof the following:
Section R302.13 exception 4 Approved floor assemblies demonstrating equivalent fire performance by an approved testing company showing length and time duration for exposure to fire. It shall be defined by performance equivalent to 26 minutes using ASTM E119 standard fire endurance testing with a superimposed load simulating a maximum load condition (i.e. 100% design load).