1020.1.1 Interior corridors.
Interior corridors shall be fire-resistance rated in accordance with Table 1020.1.1.
Exceptions:
1. A fire-resistance rating is not required for corridors in an occupancy in Group E where each room that is used for instruction has not less than one door opening directly to the exterior and rooms for assembly purposes have not less than one-half of the required means of egress doors opening directly to the exterior. Exterior doors specified in this exception are required to be at ground level and open to a public way.
2. A fire-resistance rating is not required for corridors contained within a dwelling unit or sleeping unit in an occupancy in Group R.
3. A fire-resistance rating is not required for corridors in open parking garages.
4. A fire-resistance rating is not required for corridors in an occupancy in Group B that is a space requiring only a single means of egress complying with Section 1006.2.
5. Corridors adjacent to the exterior walls of buildings shall be permitted to have unprotected openings on unrated exterior walls where unrated walls are permitted by Table 602 and unprotected openings are permitted by Table 705.8.
Occupancy | Occupant Load Served by Interior Corridor | Required Fire Resistance Rating (hours) | |
Without sprinkler system | With sprinkler system c |
Occupancy | Occupant Load Served by Interior Corridor | Required Fire Resistance Rating (hours) | |
Without sprinkler system | With sprinkler system c | ||
H-1, H-2, H-3 | All | Not Permitted | 1 |
H-4, H-5 | Greater than 30 | Not Permitted | 1 |
A, B, E, F, M,S, U | Greater than 30 | 1 | 0 |
R | Greater than 30 | 1
d
| 0 |
I-2
a
, I-4 | All | Not Permitted | 0 |
I-1, I-3 | All | Not Permitted | 1
b
|
a. For requirements for occupancies in Group I-2, see Sections 407.2 and 407.3.
b. For a reduction in the fire-resistance rating for occupancies in Group I-3, see Section 408.8.
c. Buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2 where allowed.
d. Interior corridors within dwelling or sleeping units in Group R occupancies pursuant to Section 1020.1.1, Exception 2 shall not require fire-resistance rating.
1020.1.2 Public corridors.
Public corridors shall be fire-resistance rated in accordance with Table 1020.1.2.
Occupancy | Required Fire Resistance Rating (hours) |
Occupancy | Required Fire Resistance Rating (hours) |
H-1, H-2, H-3 | 2 |
H-4, H-5 | 1 |
A, E, F, M, S, U | 1 |
B | 1
a |
R (Noncombustible) | 1
c |
R (Combustible) | 2
b |
I-1, I-2, I-3, I-4 | 1 |
a. Public corridors need not be fire-rated in high-rise buildings in occupancy Group B equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1, where such building is provided with smokeproof enclosures in stairways in accordance with Section 403.5.4.
b. Public corridors in buildings not exceeding two stories in height, or that are three stories in height and occupied by not more than one family on each story, may be constructed with one hour fire-resistance rating.
c. Corridors serving accessory rooms or spaces in Group R-2 occupancies pursuant to Section 1004.1.1.2.3 shall be constructed with fire barriers with 1-hour fire-resistance rating, and 2-hour fire-resistance rating where the dead-end distance exceeds 40 feet (12 192 mm) in length.