403.4.1 Smoke detection.
Smoke detection shall be provided in accordance with Section 907.2.13.1.
403.4.2 Fire alarm systems.
A fire alarm system shall be provided in accordance with Section 907.2.13.
403.4.3 Standpipe system.
A high-rise building shall be equipped with a standpipe system as required by Section 905.3.
403.4.4 Emergency voice/alarm communication system.
An emergency voice/alarm communication system shall be provided in accordance with Section 907.5.2.2.
403.4.5 Emergency responder radio coverage.
Emergency responder radio coverage shall be provided in accordance with the New York City Fire Code and Section 907.2.13.2 of this code.
403.4.6 Fire command.
A fire command center complying with Section 911 shall be provided in a location approved by the Fire Department.
403.4.7 Post-fire smoke purge.
A post-fire smoke purge system shall be installed in accordance with Section 917.
403.4.8 Standby and emergency power.
403.4.8.1 Equipment room.
If the standby or emergency power system includes a generator set inside a building, the system shall be located in a separate room in accordance with Section 2702.1.2.2.
403.4.8.2 Fuel line piping protection.
Fuel lines supplying a generator set inside a building shall comply with Section 1305.9 of the New York City Mechanical Code.