403.3.4 Fire pump room.
Fire pumps shall be located in rooms protected in accordance with Section 913.2.1.
403.4 Emergency systems.
The detection, alarm and emergency systems of high-rise buildings shall comply with Sections 403.4.1 through 403.4.8.
403.4.1 Smoke detection.
Smoke detection shall be provided in accordance with Section 907.2.13.1.
403.4.2 Fire alarm systems.
A fire alarm system shall be provided in accordance with Section 907.2.13.
403.4.3 Standpipe system.
A high-rise building shall be equipped with a standpipe system as required by Section 905.3.
403.4.4 Emergency voice/alarm communication system.
An emergency voice/alarm communication system shall be provided in accordance with Section 907.5.2.2.
403.4.5 Emergency responder radio coverage.
Emergency responder radio coverage shall be provided in accordance with the New York City Fire Code and Section 907.2.13.2 of this code.