424.3 Fire protection.
Children's play structures shall be provided with the same level of approved fire protection system required for other structures in the same occupancy.
424.4 Separation.
Children's play structures shall have a horizontal separation from building walls, partitions and from elements of the means of egress of not less than 5 feet (1524 mm). Children's playground structures shall have a horizontal separation from other children's play structures of not less than 20 feet (6090 mm).
424.5 Area limits.
Children's play structures shall be not greater than 300 square feet (28 m
2
) in area.
425.1 Hyperbaric facilities.
Hyperbaric facilities shall meet the requirements contained in Chapter 14 of NFPA 99.
426.1 Combustible dusts, grain processing and storage.
The provisions of Sections 426.1.1 through 426.1.7 shall apply to buildings in which materials that produce combustible dusts are stored or handled. Buildings that store or handle combustible dusts shall comply with the applicable provisions of NFPA 61, NFPA 69, NFPA 85, NFPA 120, NFPA 484, NFPA 654, NFPA 655 and NFPA 664 and the New York City Fire Code.
426.1.1 Type of construction and height exceptions.
Buildings shall be constructed in compliance with the height, number of stories and area limitations specified in Sections 504 and 506; except that where erected of Type I or II construction, the heights and areas of grain elevators and similar structures shall be unlimited, and where of Type IV construction, the maximum building height shall be 65 feet (19 812 mm) and except further that, in isolated areas, the maximum building height of Type IV structures shall be increased to 85 feet (25 908 mm).