904.6.2.3.1 Test procedure.
Hoses shall be tested at not less than 2,500 pounds per square inch (psi) (17 238 kPa) for high-pressure systems and at not less than 900 psi (6206 kPa) for low-pressure systems.
904.6.2.4 System components.
System components, such as switches, door and window releases, interconnected valves, damper releases and supplementary alarms, shall be manually operated at 12-month intervals to ensure that such components are in proper operating condition.
904.6.3 Clean agent systems.
Clean agent systems shall be maintained in accordance with FC 901.6.1, 904.5, 904.6.3.1 and 904.6.3.2.