3706.8.1 Fire guard.
A fire guard shall be required and positioned approximately every 200 feet (60 960 mm) throughout the length of the combustible fiber storage area. Persons conducting a fire watch shall have the duties and responsibilities set forth in FC 901.7.2.1 with respect to the areas being monitored in connection with combustible fiber storage, and shall be familiar with the location of fire alarm manual pull stations, and standpipe system hose and hose connections in the area.
3706.8.2 Access.
Access to combustible fibers and the aisles between the stored combustible fibers shall be restricted to personnel handling the combustible fibers, fire guards and representatives of the department.
3706.8.3 Loading and unloading.
When loading and unloading combustible fibers, two persons shall be assigned to each loading or unloading operation to stand by with the standpipe hose. These persons shall be instructed as to the location and use of the standpipe system valves and hoses.
4001.1 Scope.
This chapter governs the design, installation, operation and maintenance of distilleries, including the manufacturing, storage, handling and use of distilled spirits in such facilities. Storage of distilled spirits in a warehouse or a liquid storage warehouse that is not a distillery is governed by FC 5704.3. Any occupancy with ancillary distillery operations is a distillery regulated by this section.
Exceptions:
1. Storage of distilled spirits in a warehouse, liquid storage warehouse or other storage facility that is not a distillery is governed by FC 5704.3.
2. Bottling and related processing of distilled spirits, including blending, filtering, and other handling of distilled spirits, but excluding distilling, in a warehouse, liquid storage warehouse or other storage facility that is not a distillery, shall be conducted in accordance with FC 5705 or as otherwise provided in the rules.
4001.2 Permits.
Permits shall be required as set forth in FC 105.6.