911.3 Explosion prevention systems.
Explosion prevention systems shall be of an approved type and installed in accordance with this code and NFPA 69. Where the building or structure or part thereof is provided with a fire alarm system, explosion prevention system alarms shall be transmitted to the fire alarm system control panel and to an approved central station.
911.4 Barricades.
Barricades shall be designed and installed in accordance with NFPA 495.
912.1 Installation.
Fire department connections shall be installed in accordance with the construction codes, including the Building Code.
912.2 Location.
The location of fire department connections shall be in accordance with the Building Code.
912.2.1 Visible location.
Fire department connections shall be located on the street side of buildings, fully visible and recognizable from the street or nearest point of fire department apparatus access, or as otherwise approved by the commissioner.