904.3.7.1.3.4 Power supply.
Power supply to the alarm system shall be in accordance with applicable requirements of the Electrical Code and the construction codes, including the Building Code.
904.3.7.1.4 Pressure relief venting.
The protected area enclosure shall be provided with suitable pressure relief venting which vents outdoors.
Exception: Such venting shall not be required when a registered design professional certifies that the walls, ceilings and floors comprising the protected space have sufficient porosity and leakage to prevent damage to the integrity of such space upon discharge of the extinguishing agent, and that the inert gas agent leakage into other non-flooded rooms and spaces will not reach dangerous concentrations.
904.3.7.2 Clean agent systems.
Clean agent systems, where allowed, shall be provided with the additional safety measures set forth in FC 904.3.7.2.1 through 904.3.7.2.6.
904.3.7.2.1 System alarm and activation.
Audible and visible alarms shall be installed both inside and outside the protected area to signal the activation of an automatic detection device and the operation of the fire extinguishing system. Such signals shall continue until the atmosphere has been returned to normal. Activation of a single automatic detection device shall sound a local alarm and transmit an alarm to an approved central station. Unless the alarm is cancelled by an abort system as set forth in FC 904.3.7.2.3, activation of a second automatic detection device shall, within 30 seconds, initiate the discharge of clean agent. Power supply to the alarm system shall be in accordance with the Electrical Code, the construction codes, including the Building Code, and NFPA 2001, as modified by FC Appendix B.
904.3.7.2.2 Warning and instruction signs.
Warning and instruction signs shall be posted at entrances to and within the protected area subject to flooding.
904.3.7.2.3 Abort systems.
Abort systems may be installed only on systems activated by smoke detectors. Abort controls shall be manually operated, shall be located in the protected area, and shall cause the discharge of the clean agent after a 2-minute delay unless the abort control is reactivated for another cycle of delay. A manual pull station shall be provided which, upon activation, shall transmit an alarm to an approved central station, override the delay and cause the clean agent to discharge immediately. Abort controls shall not interfere with transmission of local alarms or central station alarms.
904.3.7.2.4 Means of egress.
Where the protected area is normally occupied, provision shall be made for adequate clear routes of exit with doors opening in direction of travel. Emergency lighting shall be provided for such exits. Exit directional signs shall clearly indicate the path of egress and exits shall be clearly marked.