913.5.3 Transfer switches.
Automatic transfer switches shall be periodically tested in accordance with FC 604 and the Electrical Code.
913.5.4 Pump room environmental conditions.
Tests of pump room environmental conditions, including heating, ventilation and illumination shall be made to ensure proper manual or automatic operation of the associated equipment.
913.6 Fire pump supervision.
The following fire pump operations shall be electrically supervised by the fire alarm system in accordance with the Electrical Code and NFPA 20; and monitored by a central station in accordance with this code and the rules:
1. Pump running.
2. Pump power failed.
3. Pump phase reversal.
914.1 General.
Yard hydrant systems shall be installed where required by the construction codes, including the Building Code, this code, including FC 507.2.3, or the rules.
914.2 Operation and maintenance.
Yard hydrant systems shall be operated and maintained in accordance with FC 901.6 and NFPA 25.
914.3 Supervision.
At all times when the area served by the yard hydrant system is in use, the system shall be under the personal supervision of a certificate of fitness holder, who shall be available to assist the department in the operation of such system.