806.1 General.
The quantity and type of interior finishes shall comply with the requirements of Chapter 8 of the Building Code.
806.2 Foam plastic signs.
Foam plastic signs that are not interior finishes shall have a maximum heat release rate of 150 kW when tested in accordance with UL 1975, or when tested in accordance with NFPA 289 using the 20 kW ignition source.
901.1 Scope.
This chapter shall govern the design, installation, operation and maintenance, including inspection and testing, of fire protection devices, equipment and systems, and other fire protection measures for the control and extinguishment of fire.
901.1.1 General.
Fire protection systems shall be designed, installed, operated and maintained in accordance with this chapter and the reference standards set forth in FC Table 901.6.1.
901.1.2 Emergency alarm systems.
Except as otherwise provided in the construction codes, this code or the rules, emergency alarm systems shall be designed, installed, operated and maintained in the same manner as fire alarm systems.