Existing underground building sewers, regardless of their age, may be reused in accordance with Section 18-29-301.3.
(Amend Coun. J. 11-8-12, p. 38872, § 357; Amend Coun. J. 7-29-15, p. 3537, § 4; Amend Coun. J. 10-14-21, p. 37722, Art. VII, § 3)
Horizontal drainage piping shall be installed in uniform alignment at uniform slopes. The minimum slope of a horizontal drainage pipe shall be in accordance with Table 18-29-704.1.
Size (inches) | Minimum Slope (inch per foot) |
2 1/2 or less | 1/4 |
3 to 6 | 1/8 |
8 or larger | 1/16 |
Horizontal branches shall connect to the bases of stacks at a point located not less than 10 pipe diameters downstream from the stack. Except as prohibited by Section 18-29-711.2, horizontal branches shall connect to horizontal stack offsets at a point located not less than 10 pipe diameters downstream from the upper stack.