Loading...
Horizontal drainage piping shall be installed in uniform alignment at uniform slopes. The minimum slope of a horizontal drainage pipe shall be in accordance with Table 18-29-704.1.
Size (inches) | Minimum Slope (inch per foot) |
2 1/2 or less | 1/4 |
3 to 6 | 1/8 |
8 or larger | 1/16 |
Horizontal branches shall connect to the bases of stacks at a point located not less than 10 pipe diameters downstream from the stack. Except as prohibited by Section 18-29-711.2, horizontal branches shall connect to horizontal stack offsets at a point located not less than 10 pipe diameters downstream from the upper stack.