18-29-713.11.1 Bedpan steamers.
   The minimum size of a sterilizer vent serving a bedpan steamer shall be 1 1/2 inches (38 mm) in diameter. Multiple installations shall be sized in accordance with Table 18-29-713.11.1.
Table 18-29-713.11.1
Stack Sizes for Bedpan Steamers and Boiling Type Sterilizers (Number of Connections of Various Sizes Permitted to Various-Sized Sterilizer Vent Stacks)
Stack Size (inches)
Connection Size
1 1/2"
2"
Stack Size (inches)
Connection Size
1 1/2"
2"
1 1/2 a
1
or
0
2 a
2
or
1
2 b
1
or
1
3 a
4
or
2
3 b
2
or
2
4 a
8
or
4
4 b
4
or
4
 
For SI: 1 inch = 25.4 mm.
a.   Total of each size.
b.   Combination of sizes.
18-29-713.11.2 Boiling-type sterilizers.
   The minimum size of a sterilizer vent stack shall be 2 inches (51 mm) in diameter where serving a utensil sterilizer and 1 1/2 inches (38 mm) in diameter where serving an instrument sterilizer. Combinations of boiling-type sterilizer vent connections shall be sized in accordance with Table 18-29-713.11.1.
18-29-713.11.3 Pressure sterilizers.
   Pressure sterilizer vent stacks shall be 2 1/2 inches (64 mm) minimum. Those serving combinations of pressure sterilizer exhaust connections shall be sized in accordance with Table 18-29-713.11.3.
Table 18-29-713.11.3
Stacks Sizes for Pressure Sterilizers (Number of Connections of Various Sizes Permitted to Various- Sized Vent Stacks)
Stack Size (inches)
Connection Size
3/4"
1"
1 1/4"
1 1/2"
Stack Size (inches)
Connection Size
3/4"
1"
1 1/4"
1 1/2"
1 1/2 a
3 or
2 or
1
1 1/2 b
2 and
1
2 a
6 or
3 or
2 or
1
2 b
3 and
2
2 b
2 and
1 and
1
2 b
1 and
1 and
1
3 a
15 or
7 or
5 or
3
3 b
1 and
1 and
5 and
2 and
2
1
 
For SI: 1 inch = 25.4 mm.
a.   Total of each size.
b.   Combination of sizes.
18-29-713.11.4 Pressure instrument washer sterilizer sizes.
   The minimum diameter of a sterilizer vent stack serving an instrument washer sterilizer shall be 2 inches (50 mm). Not more than two sterilizers shall be installed on a 2-inch (50 mm) stack, and not more than four sterilizers shall be installed on a 3-inch (75 mm) stack.
18-29-714 Deliberately omitted.
18-29-715 Backwater Valves.
18-29-715.1 Sewage backflow.
   A backwater valve shall be installed only for plumbing fixtures where the overflow rim of the lowest plumbing fixtures are below the next upstream manhole in the public sewer. Plumbing fixtures with flood rims above the next upstream manhole shall not discharge through the backwater valve.
18-29-715.2 Fixture branches.
   Backwater valves shall be installed in the branch of the building drain that receives only the discharge from fixtures located within such branch and shall be located below ground.