Pressure sterilizer vent stacks shall be 2 1/2 inches (64 mm) minimum. Those serving combinations of pressure sterilizer exhaust connections shall be sized in accordance with Table 18-29-713.11.3.
Stack Size (inches) | Connection Size | |||
3/4" | 1" | 1 1/4" | 1 1/2" |
Stack Size (inches) | Connection Size | |||
3/4" | 1" | 1 1/4" | 1 1/2" | |
1 1/2 a | 3 or | 2 or | 1 | – |
1 1/2 b | 2 and | 1 | – | – |
2 a | 6 or | 3 or | 2 or | 1 |
2 b | 3 and | 2 | – | – |
2 b | 2 and | 1 and | 1 | – |
2 b | 1 and | 1 and | – | 1 |
3 a | 15 or | 7 or | 5 or | 3 |
3 b | 1 and | 1 and 5 and | 2 and | 2 1 |
For SI: 1 inch = 25.4 mm.
a. Total of each size.
b. Combination of sizes.