Cleanouts shall be the same nominal size as the pipe they serve up to 4 inches (100 mm). For pipes larger than 4 inches (100 mm) nominal size, the minimum size of the cleanout shall be 4 inches (100 mm).
Exception: "P" trap connections with slip joints or ground joint connections, or stack cleanouts that are no more than one pipe diameter smaller than the drain served, shall be approved.
For building sewers 8 inches (200 mm) and larger nominal size, manholes shall be provided and located at each change in direction greater than 45 degrees, and at the locations and intervals referenced in the current edition of the permit requirement and fees book.