175.62 SECTION 1807.1.5.1 ADDITION - FOUNDATION WALLS FOR CONVENTIONAL LIGHT FRAME WOOD CONSTRUCTION.
Section 1807.1.5.1, Foundation Walls For Conventional Light Frame Wood Construction, of the IBC, is hereby established by adding the following section and table:
Section 1807.1.5.1 Foundation Walls For Conventional Light Frame Wood Construction As an alternate to the requirements of this code the following Table 'Foundation Walls for Conventional Light Frame Construction' may be used:
Table - ‘Foundation Walls for Conventional Light Frame Construction’
Height of Foundation Wall (Net measured from top of basement slab to top of foundation wall)*
Thickness of Foundation Walls
Reinforcement type and placement within Foundation Wall**
Reinforcement type and placement within Foundation Wall** (maximum 12’ span between corners and supporting cross walls)
Type of Mortar
Unit
Gross
Net
Concrete
Masonry
Concrete
Masonry
Masonry
Height of Foundation Wall (Net measured from top of basement slab to top of foundation wall)*
Thickness of Foundation Walls
Reinforcement type and placement within Foundation Wall**
Reinforcement type and placement within Foundation Wall** (maximum 12’ span between corners and supporting cross walls)
Type of Mortar
Unit
Gross
Net
Concrete
Masonry
Concrete
Masonry
Masonry
8
7’ 8”
7 ½”
8”
½” horizontal bars, placement in the middle, and near the top & bottom – ½” bars @ 6’ max. vertically
0.075 square inch bar 8’ o.c. vertically in fully grouted cells. If block is 12” nominal thickness, may be unreinforced.
Type M or S. Grout & Mortar shall meet provisions of Chapter 21 IBC
9
8’ 8”
8”
See Chapter 18 IBC
½” bars 2’ o.c. horizontally & 20” vertically o.c.
(5/8” bars 2’ o.c. horizontally & 30” vertically o.c.)
See Chapter 18 IBC
Same as above
10
9’ 8”
8”
See Chapter 18 IBC
See Chapter 18 IBC
Same as above
*Concrete floor slab to be nominal 4”. If such floor slab is not provided prior to backfill, provide 1) 36” vertical #4 rebar embedded in the footing @ maximum 7’ O.C. spacing -and/or- 2) full depth nominal 2”depth x 4”width keyway in footing
** All reinforcement bars shall meet ASTM A6175 grade 40 minimum and be deformed. Placement of bars shall be in center of wall and meet the provisions of 18, 19, and 21 of the International Building Code.
NOTE: Cast in place concrete shall have a compressive strength of 3,000 lbs @ 28 days. Footings shall contain continuous reinforcement of 2 – ½” diameter rebar throughout. Placement of reinforcement and concrete shall meet the requirements of Chapter 19 of the International Building Code.
NOTE: Material used for backfilling shall be carefully placed granular soil of average or high permeability and shall be drained with an approved drainage system as prescribed in Section 1805.4 of the International Building Code. Where soils containing a high percentage of clay, fine silt or similar materials of low permeability or expansive soils are encountered or where backfill materials are not drained or an unusually high surcharge is to be placed adjacent to the wall, a specially designed wall shall be required.
Note: Foundation plate or sill anchorage may be installed in accordance with the respective codes as applicable.