175.38 SECTION 907.1.4 ADDITION - FACP (Fire Alarm Control Panels).
Section 907.1.4, FACP ) Fire Alarm Control Panels) is hereby established by adding the following section and exception:
Section 907.1.4 FACP (Fire Alarm Control Panels) Each building shall have no more than 1 FACP.
Installation of fire alarm panel shall be not exceed six feet in height measured from the floor to the top of the unit.
Exception: Suppression system releasing panels are not required to meet the height requirement or the limitation in the number of panels.