Section 508.5.2, Occupancies, of the IBC, is hereby amended by numbering the existing exception as #1 and thereafter adding the following exception #2:
Section 508.5.2 Occupancies
2. Live/work units located within detached one- and two-family dwellings and townhouses may be constructed in accordance with the International Residential Code.
Section 707.5, Continuity, of the IBC, is hereby amended by adding the following exception #4:
Section 707.5 Continuity exception
4. Shafts required to be constructed as per section 713.3.2 having exterior walls that are not required to be fire rated per section 707.4 shall be permitted to be constructed of materials permitted by the building type of construction so long as a complete non-combustible separation of 2 hours is provided between the shaft and adjoining structure. In addition, the provisions of section 1023.7 shall be met.
Section 713.3.1, One-Hour Shaft Enclosures, of the IBC, is hereby established by adding the following section:
Section 713.3.1 One-hour Shaft Enclosures Shafts that are allowed to have a fire resistance rating of 1 hour or less are allowed to be constructed of materials permitted by the building type of construction.
Section 713.3.2, Two-Hour Shaft Enclosures, of the IBC, is hereby established by adding the following section:
Section 713.3.2 Two-Hour Shaft Enclosures Shafts that are required to have a fire resistance rating of 2 hours or more serving Interior Exit Stairs or Interior Exit Ramps shall be constructed of concrete or masonry for types III, IV and V construction. Interior Exit Stairs or Interior Exit Ramps in type I and II construction and all other shafts that are required to have a fire resistance rating of 2 hours or more shall be constructed of non-combustible materials.
Section 903.2.11.1.3, Basements, of the IBC, is hereby amended by deleting said section and inserting in lieu thereof the following:
Section 903.2.11.1.3 Basements Where any portion of a basement is located more than 75 feet (22 860 mm) from openings required by Section 903.2.11.1, the basement shall be equipped throughout with an approved automatic sprinkler system.
Section 903.4.2, Alarms, of the IBC, is hereby amended by deleting said section and inserting in lieu thereof the following section:
Section 903.4.2 Alarms An approved weather proof audible device suitable for outdoor use with 110 candela visual signal shall be connected to every automatic sprinkler system. Such sprinkler water-flow alarm devices shall be activated by water flow equivalent to the flow of a single sprinkler of the smallest orifice size installed in the system. Alarm devices shall be provided on the exterior of the building in an approved location. Where a fire alarm system is installed, actuation of the automatic sprinkler system shall actuate the building fire alarm system.
Section 907.1.4, FACP ) Fire Alarm Control Panels) is hereby established by adding the following section and exception:
Section 907.1.4 FACP (Fire Alarm Control Panels) Each building shall have no more than 1 FACP.
Installation of fire alarm panel shall be not exceed six feet in height measured from the floor to the top of the unit.
Installation of fire alarm panel shall be not exceed six feet in height measured from the floor to the top of the unit.
Exception: Suppression system releasing panels are not required to meet the height requirement or the limitation in the number of panels.