415.11.7 Continuous gas detection systems.
A continuous gas detection system shall be provided for HPM gases where the physiological warning threshold level of the gas is at a higher level than the accepted permissible exposure limit (PEL) for the gas and for flammable gases in accordance with Sections 415.11.7.1 and 415.11.7.2.
415.11.7.1 Where required.
A continuous gas detection system shall be provided in the areas identified in Sections 415.11.7.1.1 through 415.11.7.1.4.
415.11.7.1.1 Fabrication areas.
A continuous gas detection system shall be provided in fabrication areas where gas is used in the fabrication area.
415.11.7.1.2 HPM rooms.
A continuous gas detection system shall be provided in HPM rooms where gas is used in the room.
415.11.7.1.3 Gas cabinets, exhausted enclosures and gas rooms.
A continuous gas detection system shall be provided in gas cabinets and exhausted enclosures. A continuous gas detection system shall be provided in gas rooms where gases are not located in gas cabinets or exhausted enclosures.