415.11.1 Fabrication areas.
Fabrication areas shall comply with Sections 415.11.1.1 through 415.11.1.8.
415.11.1.1 Hazardous materials.
Hazardous materials and hazardous production materials (HPM) shall comply with Sections 415.11.1.1.1 through 415.11.1.1.2.
415.11.1.1.1 Aggregate quantities.
The aggregate quantities of hazardous materials stored and used in a single fabrication area shall not exceed the quantities set forth in Table 415.11.1.1.1.
Exception: The quantity limitations for any hazard category in Table 415.11.1.1.1 shall not apply where the fabrication area contains quantities of hazardous materials not exceeding the maximum allowable quantities per control area established by Tables 307.1(1) and 307.1(2).
Hazard Category | Solids (pounds per square foot) | Liquids (gallons per square foot) | Gas (cubic feet @ NTP/square foot) |
Hazard Category | Solids (pounds per square foot) | Liquids (gallons per square foot) | Gas (cubic feet @ NTP/square foot) |
Physical-Hazard Materials | |||
Combustible dust | Note b | Not Applicable | Not Applicable |
Combustible fiber Loose Baled | Note b Notes b, c | Not Applicable | Not Applicable |
Combustible liquid II IIIA IIIB Combination Class I, II and IIIA | Not Applicable | 0.01 0.02 Not Limited 0.04 | Not Applicable |
Cryogenic gas Flammable Oxidizing | Not Applicable | Not Applicable | Note d 1.25 |
Explosives | Note b | Note b | Note b |
Flammable gas Gaseous Liquefied | Not Applicable | Not Applicable | Note d Note d |
Flammable liquid IA IB IC Combination Class IA, IB and IC Combination Class I, II and IIIA | Not Applicable | 0.0025 0.025 0.025 0.025 0.04 | Not Applicable |
Flammable solid | 0.001 | Not Applicable | Not Applicable |
Organic peroxide Unclassified detonable Class I Class II Class III Class IV Class V | Note b Note b 0.025 0.1 Not Limited Not limited | Not Applicable | Not Applicable |
Oxidizing gas Gaseous Liquefied Combination of gaseous and liquefied | Not Applicable | Not Applicable | 1.25 1.25 1.25 |
Oxidizer Class 4 Class 3 Class 2 Class 1 Combination Class 1, 2, 3 | Note b 0.003 0.003 0.003 0.003 | Note b 0.03 0.03 0.03 0.03 | Not Applicable |
Pyrophoric material | 0.01 | 0.00125 | Notes d and e |
Unstable reactive Class 4 Class 3 Class 2 Class 1 | Note b 0.025 0.1 Not Limited | Note b 0.0025 0.01 Not Limited | Note b Note b Note b Not Limited |
Water reactive Class 3 Class 2 Class 1 | Note b 0.25 Not Limited | 0.00125 0.025 Not Limited | Not Applicable |
Health-Hazard Materials | |||
Corrosives | Not Limited | Not Limited | Not Limited |
Highly toxic | Not Limited | Not Limited | Note d |
Toxics | Not Limited | Not Limited | Note d |
For SI: 1 pound per square foot = 4.882 kg/m2, 1 gallon per square foot = 40.7 L/m2, 1 cubic foot @ NTP/square foot = 0.305 m
3 @ NTP/m2, 1 cubic foot = 0.02832 m
3
a. Hazardous materials within piping shall not be included in the calculated quantities.
b. Quantity of hazardous materials in a single fabrication shall not exceed the maximum allowable quantities per control area in Tables 307.1(1) and 307.1(2).
c. Densely packed baled cotton that complies with the packing requirements of ISO 8115 shall not be included in this material class.
d. The aggregate quantity of flammable, pyrophoric, toxic and highly toxic gases shall not exceed 9,000 cubic feet at NTP.
e. The aggregate quantity of pyrophoric gases in the building shall not exceed the amounts set forth in Table 415.6.2.
415.11.1.1.2 Hazardous production materials.
The maximum quantities of hazardous production materials (HPM) stored in a single fabrication area shall not exceed the maximum allowable quantities per control area established by Tables 307.1(1) and 307.1(2).
415.11.1.2 Separation.
Fabrication areas, whose sizes are limited by the quantity of hazardous materials allowed by Table 415.11.1.1.1, shall be separated from each other, from corridors and from other parts of the building by not less than 1-hour fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 711, or both.
Exceptions:
1. Doors within such fire barrier walls, including doors to corridors, shall be only self-closing fire door assemblies having a fire protection rating of not less than 3/4 hour.
2. Windows between fabrication areas and exit access corridors are permitted to be fixed glazing listed and labeled for a fire protection rating of not less than 3/4 hour in accordance with Section 716.
415.11.1.3 Location of occupied levels.
Occupied levels of fabrication areas shall be located at or above the first story above grade plane.
415.11.1.4 Floors.
Except for surfacing, floors within fabrication areas shall be of noncombustible construction.
Openings through floors of fabrication areas are permitted to be unprotected where the interconnected levels are used solely for mechanical equipment directly related to such fabrication areas (see also Section 415.11.1.5).
Floors forming a part of an occupancy separation shall be liquid tight.