415.8.2 Separation of incompatible materials.
Hazardous materials other than those listed in Table 415.6.2 shall be allowed in manufacturing, processing, dispensing, use or storage areas when separated from incompatible materials in accordance with the provisions of the New York City Fire Code.
415.8.3 Water reactives.
Group H-2 and H-3 occupancies containing water-reactive materials shall be resistant to water penetration. Piping for conveying liquids shall not be over or through areas containing water reactives, unless isolated by approved liquid-tight construction.
Exception: Fire protection piping shall be permitted over or through areas containing water reactives without isolating it with liquid-tight construction.
415.8.4 Floors in storage rooms.
Floors in storage areas for organic peroxides, oxidizers, pyrophoric materials, unstable (reactive) materials and water-reactive solids and liquids shall be of liquid-tight, noncombustible construction.
415.8.5 Waterproof room.
Rooms or areas used for the storage of water-reactive solids and liquids shall be constructed in a manner that resists the penetration of water through the use of waterproof materials. Piping carrying water for other than approved automatic fire sprinkler systems shall not be within such rooms or areas.
415.9 Group H-2.
Occupancies in Group H-2 shall be constructed in accordance with the New York City Fire Code and Sections 415.9.1 through 415.9.3 of this code.
415.9.1 Flammable and combustible liquids.
The storage, handling, processing and transporting of flammable and combustible liquids in Group H-2 and H-3 occupancies shall be in accordance with the New York City Mechanical Code, the New York City Fire Code, and Sections 415.9.1.1 through 415.9.1.9 of this code.