410.3.7.2 Smoke control.
Smoke control in accordance with Section 909 shall be provided to maintain the smoke layer interface not less than 6 feet (1829 mm) above the highest level of the assembly seating or above the top of the proscenium opening where a proscenium wall is provided in compliance with Section 410.3.4.
410.4 Platform construction.
Permanent platforms shall be constructed of materials as required for the type of construction of the building in which the permanent platform is located. Permanent platforms are permitted to be constructed in accordance with the following:
1. The area below the platform shall be enclosed on all sides with solid construction.
2. Platforms constructed of untreated wood shall not exceed an area of 400 square feet (37 m
2
). Platforms constructed of fire retardant treated wood shall not exceed an area of 1,200 square feet (111 m
2
). Platforms constructed of noncombustible materials shall not be limited in area.
3. Where wood is used, the floor of the platform shall be a least 1 inch (25 mm) nominal thickness. Such floor shall be laid on a solid, noncombustible backing, or shall have all spaces between supporting members fire blocked with noncombustible material.
Where the space beneath the permanent platform is used for storage or any other purpose other than equipment, wiring or plumbing, the floor construction shall not be less than 1-hour fire-resistant construction. Where the space beneath the permanent platform is used only for equipment, wiring or plumbing, the underside of the permanent platform need not be protected.
410.4.1 Temporary platforms.
Platforms installed for a period of not more than 30 days are permitted to be constructed of any materials permitted by this code. The space between the floor and the platform above shall only be used for plumbing and electrical wiring to platform equipment.
410.5 Dressing and appurtenant rooms.
Dressing and appurtenant rooms shall comply with Sections 410.5.1 and 410.5.2.
410.5.1 Separation from stage.
The stage shall be separated from dressing rooms, scene docks, property rooms, workshops, storerooms and compartments appurtenant to the stage and other parts of the building by fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 711, or both. The fire-resistance rating shall be not less than 2 hours for stage heights greater than 50 feet (15 240 mm) and not less than 1 hour for stage heights of 50 feet (15 240 mm) or less.
410.5.2 Separation from each other.
Dressing rooms, scene docks, property rooms, workshops, storerooms and compartments appurtenant to the stage shall be separated from each other by not less than 1-hour fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 711, or both.
410.6 Means of egress.
Except as modified or as provided for in this section, the provisions of Chapter 10 shall apply.
410.6.1 Stage exits.
No fewer than one exit or exit access doorway shall be provided from each side of the stage and from each side of the space under the stage. Technical production areas shall comply with Section 410.6.3.
410.6.2 Stairway and ramp enclosure.
Exit access stairways and ramps serving a stage or platform are not required to be enclosed. Exit access stairways and ramps serving technical production areas are not required to be enclosed.