1809.5.7.6 Dewatering.
Where piers are carried to depths below the groundwater level, the piers shall be constructed by a method that will provide accurate preparation and inspection of the subgrade in dry conditions.
1809.5.8 Foundation walls.
Concrete and masonry foundation walls shall be designed in accordance with Chapter 19 or 21, respectively.
1809.5.8.1 Foundation wall thickness.
The minimum thickness of concrete and masonry foundation walls shall comply with Section 1809.5.8.1.1.
1809.5.8.1.1 Thickness based on walls supported.
The thickness of foundation walls shall not be less than the thickness of the wall supported, except that foundation walls of at least 8 inch (203.2 mm) nominal width are permitted to support brick-veneered frame walls and 10 inch wide (254 mm) cavity walls.
1809.5.8.2 Foundation wall drainage.
Foundation walls shall be designed to support the weight of the full hydrostatic pressure of undrained backfill unless a drainage system is installed in accordance with Sections 1805.4.2 and 1805.4.3.