18-29-308.5 Interval of support.
   Pipe shall be supported in accordance with Table 18-29-308.5.
Table 18-29-308.5
Hanger Spacing
 
Piping Material
Maximum Horizontal Spacing (feet)
Maximum Vertical Spacing (feet)
Cast-iron pipe
5 a
15
Copper or copper-alloy pipe
12
10
Copper or copper-alloy tubing,
1 1/4-inch diameter and smaller
6
10
Copper or copper-alloy tubing,
1 1/2-inch diameter and larger
10
10
Polyvinyl chloride (PVC) pipe
4
10 b
Stainless steel drainage systems
10
10 b
 
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
a.   The maximum horizontal spacing of cast-iron pipe hangers shall be increased to 10 feet where 10-foot lengths of pipe are installed.
b.   For sizes 2 inches and smaller, a guide shall be installed midway between required vertical supports. Such guides shall prevent pipe movement in a direction perpendicular to the axis of the pipe.
(Amend Coun. J. 3-27-02, p. 82090, § 3; Amend Coun. J. 10-14-21, p. 37722, Art. III, § 17)