Loading...
18-29-314.2 Evaporators and cooling coils.
   Condensate drain systems shall be provided for equipment and appliances containing evaporators or cooling coils. Condensate drain systems shall be designed, constructed and installed in accordance with Sections 18-29-314.2.1 through 18-29-314.2.5.
(Added Coun. J. 10-14-21, p. 37722, Art. III, § 24)
18-29-314.2.1 Condensate disposal.
   Condensate from all cooling coils and evaporators shall be conveyed from the drain pan outlet to an appropriate place of disposal. Such piping shall maintain a horizontal slope in the direction of discharge of not less than one-eighth unit vertical in 12 units horizontal (1-percent slope). Condensate shall not discharge into a street, alley or other area so as to cause a nuisance.
(Added Coun. J. 10-14-21, p. 37722, Art. III, § 24)
18-29-314.2.2 Drain pipe materials and sizes.
   Components of the condensate disposal system shall be cast iron, galvanized steel, copper and copper alloy, cross-linked polyethylene, polyethylene, CPVC, PVC or polypropylene pipe or tubing. Components shall be selected for the pressure and temperature rating of the installation. Joints and connections shall be made in accordance with the applicable provisions of Chapter 7 relative to the material type. Condensate waste and drain line size shall be not less than 3/4-inch (19.1 mm) internal diameter and shall not decrease in size from the drain pan connection to the place of condensate disposal. Where the drain pipes from more than one unit are manifolded together for condensate drainage, the pipe or tubing shall be sized in accordance with Table 18-29-314.2.2.
Table 18-29-314.2.2
Condensate Drain Sizing
 
EQUIPMENT CAPACITY
MINIMUM CONDENSATE PIPE DIAMETER
Up to 20 tons
of refrigeration
3/4 inch
Over 20 tons to 40 tons
of refrigeration
1 inch
Over 40 tons to 90 tons
of refrigeration
1 1/4 inch
Over 90 tons to 125 tons
of refrigeration
1 1/2 inch
Over 125 tons to 250 tons
of refrigeration
2 inch
 
For SI: 1 inch = 25.4 mm, 1 ton of capacity = 3.517 kW.
(Added Coun. J. 10-14-21, p. 37722, Art. III, § 24)
18-29-314.2.3 Auxiliary and secondary drain systems.
   In addition to the requirements of Section 18-29-314.2.1, where damage to any building components could occur as a result of overflow from the equipment primary condensate removal system, one of the following auxiliary protection methods shall be provided for each cooling coil or fuel-fired appliance that produces condensate:
   1.   An auxiliary drain pan with a separate drain shall be provided under the coils on which condensation will occur. The auxiliary pan drain shall discharge to a conspicuous point of disposal to alert occupants in the event of a stoppage of the primary drain. The pan shall have a depth of not less than 1 1/2 inches (38 mm), shall be not less than 3 inches (76 mm) larger than the unit or the coil dimensions in width and length and shall be constructed of corrosion-resistant material. Galvanized sheet metal pans shall have a thickness of not less than 0.0236-inch (0.6010 mm) (No. 24 gage) galvanized sheet metal. Nonmetallic pans shall have a thickness of not less than 0.0625 inch (1.6 mm).
   2.   A separate overflow drain line shall be connected to the drain pan provided with the equipment. Such overflow drain shall discharge to a conspicuous point of disposal to alert occupants in the event of a stoppage of the primary drain. The overflow drain line shall connect to the drain pan at a higher level than the primary drain connection.
   3.   An auxiliary drain pan without a separate drain line shall be provided under the coils on which condensate will occur. Such pan shall be equipped with a water-level detection device conforming to UL 508 that will shut off the equipment served prior to overflow of the pan. The auxiliary drain pan shall be constructed in accordance with Item 1 of this section.
   4.   A water-level detection device conforming to UL 508 shall be provided that will shut off the equipment served in the event that the primary drain is blocked. The device shall be installed in the primary drain line, the overflow drain line or in the equipment-supplied drain pan, located at a point higher than the primary drain line connection and below the overflow rim of such pan.
   Exception: Fuel-fired appliances that automatically shut down operation in the event of a stoppage in the condensate drainage system.
(Added Coun. J. 10-14-21, p. 37722, Art. III, § 24)
18-29-314.2.3.1 Water-level monitoring devices.
   On down-flow units and all other coils that do not have a secondary drain or provisions to install a secondary or auxiliary drain pan, a water-level monitoring device shall be installed inside the primary drain pan. This device shall shut off the equipment served in the event that the primary drain becomes restricted. Devices installed in the drain line shall not be permitted.
(Added Coun. J. 10-14-21, p. 37722, Art. III, § 24)
18-29-314.2.3.2 Appliance, equipment and insulation in pans.
   Where appliances, equipment or insulation are subject to water damage when auxiliary drain pans fill, such portions of the appliances, equipment and insulation shall be installed above the flood level rim of the pan. Supports located inside of the pan to support the appliance or equipment shall be water resistant.
(Added Coun. J. 10-14-21, p. 37722, Art. III, § 24)
18-29-314.2.4 Traps.
   Condensate drains shall be trapped as required by the equipment or appliance manufacturer.
(Added Coun. J. 10-14-21, p. 37722, Art. III, § 24)
18-29-314.2.4.1 Ductless mini-split system traps.
   Ductless mini-split equipment that produces condensation shall be provided with an in-line check valve located in the drain line or a trap.
(Added Coun. J. 10-14-21, p. 37722, Art. III, § 24)
18-29-314.2.5 Drain line maintenance.
   Condensate drain lines shall be configured to permit the clearing of blockages and performance of maintenance without requiring the drain line to be cut.
(Added Coun. J. 10-14-21, p. 37722, Art. III, § 24)
Loading...