502.3 Battery-charging areas for powered vehicles and equipment.
Ventilation shall be provided in an approved manner in battery-charging areas to prevent a dangerous accumulation of flammable gases.
Exception: Lithium-ion batteries shall not require ventilation.
502.4 Stationary storage battery systems.
Stationary storage battery systems, as regulated by Section 608 of the New York City Fire Code, shall be provided with ventilation in accordance with this chapter, Section 502.4.3 and either Section 502.4.1 or 502.4.2.
Exception: Lithium-ion batteries shall not require ventilation.
502.4.1 Hydrogen limit in rooms.
For flooded lead acid, flooded nickel cadmium and VRLA batteries, the ventilation system shall be designed to limit the maximum concentration of hydrogen to 1.0 percent of the total volume of the room.
502.4.2 Ventilation rate in rooms.
Continuous ventilation shall be provided at a rate of not less than 1 cubic foot per minute per square foot (cfm/ft
2
) (0.00508 m
3
/(s • m
2
)) of floor area of the room.
502.4.3 Supervision.
Mechanical ventilation systems required by Section 502.4 shall be supervised with proof of airflow by a central, proprietary system or remote station service or shall initiate an audible and visual signal at a constantly attended on-site location.