709.3 Caution sign.
A sign stating, "Louvers, dampers and/or ventilation openings must not be blocked or disabled." shall be permanently affixed, in clear view, and adjacent to the opening(s) within the room containing the equipment. The letters used on the sign shall be at least 1 inch (25.4 mm) in height.
710.1 General.
Combustion air openings to the outdoors shall comply with the location and protection provisions applicable to outside air intake openings of Sections 401.5 and 401.6.
801.1 Scope.
This chapter shall govern the installation, maintenance, design, minimum safety requirements, repair and approval of factory-built chimneys, chimney liners, vents and connectors, and field built chimneys and connectors for all nongas-fired appliances. This chapter shall also govern the utilization of masonry chimneys. Gas-fired appliances shall be vented in accordance with the New York City Fuel Gas Code. The construction, repair, maintenance and approval of masonry chimneys shall be regulated by the New York City Building Code. Venting systems shall be designed in accordance with this chapter and comply with the requirements of the New York City Air Pollution Control Code.
801.1.1 Existing chimneys and vents.
Existing chimneys and vents shall comply with the requirements of Section 28-104.13 of the New York City Administrative Code and Sections 801.1.1.1 through 801.1.1.8 of this code.