511.2 Exhaust outlets.
Outlets for exhaust that exceed 600°F (315°C) shall be designed as a chimney in accordance with Table 511.2.
Serving Temperature Range | Minimum Thickness | Termination | Clearance | |||||||
Walls (inch) | Lining | Above roof opening (feet) | Above any part of building within (feet) | Combustible construction (inches) | Noncombustible construction | |||||
10 | 25 | 50 | Interior inst. | Exterior inst. | Interior inst. | Exterior inst. | ||||
High-heat appliances (Over 2,000°F) a | 0.127 (No. 10 MSG) | 4 1/2" laid on 4 1/2" bed | 20 | — | — | 20 | See Note c | |||
Low-heat appliances (1,000°F normal operation) | 0.127 (No. 10 MSG) | None | 3 | 2 | — | — | 18 | 6 | Up to 18" diameter, 2" Over 18" diameter, 4" | |
Medium-heat appliances (2,000°F maximum) b | 0.127 (No. 10 MSG) | Up to 18" dia. – 2 1/2" Over 18" – 4 1/2" On 4 1/2" bed | 10 | — | 10 | — | 36 | 24 | Up to 18" diameter, 2" Over 18" diameter, 4" |
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, °C = ((°F) - 32)/1.8.
a. Lining shall extend from bottom to top of outlet.
b. Lining shall extend from 24 inches below connector to 24 feet above.
c. Clearance shall be as specified by the design engineer and shall have sufficient clearance from buildings and structures to avoid overheating combustible materials (maximum 160°F).
512.1 General.
Where a subslab soil exhaust system is provided, the duct shall conform to the requirements of this section.